SG(B)10-100

Production introduction
Our company has developed this product by ourselves.As a high performance,high safety,pollution free dry-type transformer,it is suitable for the harsh environments where there is a high fire protection requirement,the great load fluctuation and the site where is of filth and moisture.For example:airport,power plant,metallurgy operation,hospital,high building shopping center,densely inhabited ared,petrochemical industry,nuclear power station and nuclear submarine,elc. 


Normal service conditions
1.A unique ceramic type of insulation structure is adopted in H-class high strength insulation cylinders and high-frequency ceramic cushion blocks are adopted to ensure that no deformation will occur.
2.The high-voltage and low-voltage windings are made of NOMEX wrapped flat copper wires and imported copper foils.And they are sealed with high strength insulation materials.
3.The iron core is made of laminated imported high-quality silicon-steel sheets of high magnetic conductivity with a 45 stepwise all-bias structure.A flexible fastening unit is adopted to fasten the winding and iron core,which ensures a relatively low no-load loss and low noise.
4.Outlet terminals are fixed to the top of winding,taps are in the middle of winding,low-voltage line terminal are in plate-type current-conducting rows for which cold pressure welding is adopted.

Normal service conditions
1)Altitude should not be over 1000m:indoor type
2)Highest ambient temperature should not over:+40oC;Highest daily average should not over temperature:+30oC
3)Highest annual average temperature should not over +20oC,lowest temperature should not below -5oC,We can provide transformer operated in special conditions according to users requirement.

Model designation


Applicable standards
GB6450-1986 Dry-type power transformer
GB/T10228-1997 Technical parameters and requirements for dry-type power transformer
GB/T17211-1998 Guide rules for dry-type power transformer load
GB10237-1998 Insulation level and insulation test for power transformer
GB4208-1993 Casing protection grade(IP code)
JB/10008-1999 6~220KV transformer sound level
JB/T56009-1998 Product quality grading for dry-type power transformer

Performance characteristics
1.Excellent heat dissipation,long thermal life,good overload capacity,without forced air-cooling under a long-term 120% overload and IP45 condition.It can operate for a long time at full load.
2.Extremely high safety fire resistance performance,smoke-free while burning under a temperature as high as 800oC.
3.Extremely high thremal shock resistance capacity.
4.100% water-proof,excellent moisture -proof.
5.Unique winding structure and field strength calculation makes partial discharge impossible.
6.Low loss and significant energy saving effect.Compared with SC9 series of dry-type transformers,the no-load loss falls 10% and load loss falls 5% in average.
7.The insulation material and copper conductor can be dismantled easily and recycled after the service life. Therefore,no pollution will occur.

Notes for placing orders
Transformer type:rated capacity kVA
Number of phases:three-phase∉ single-phase∉
High voltage: KV/Low voltage:KV
Frequency:50HZ∉ 60HZ∉
Tapping range:±4×2.5%∉ ±3×2.5%∉ other∉
Connection group:Yyn0∉ Dyn11∉ other∉
Impedance voltage:4%∉ 6%∉ other∉
Cooling method: ONAN∉ ONAF∉
Protecting grade of outer casing:IP00∉ IP20∉ IP30∉ other∉

Method of incoming and outgoing line:
1.Incoming line to lower part and outgoing line from upper part∉
2.Incoming line to upper part and outgoing line form upper part∉
3.Incoming line to upper part and outgoing line form side part∉
4.other∉
*If customer has no requirement,the color of outer casing is light grey(the standard color of ANDELI),or you sould indicate color code that you want∉

Main technical parameters of SG(B)10-100~2500/10 series of transformers

Rated capacity(KVA) Voltage combination(KV) Connecting groupid No-load lossess (W) Load-loss (W) (120oC) Load-loss (W) (75oC) Short circuit impedance (%) No-load current (%) Yawp grade (Db) IP00(no crust) IP20(IP23) High voltage connection end(mm) Low voltage connectionend (mm)
High voltage (KV) Tapping (%) Low voltage (KV) Length (mm) Width (mm) Height (mm) Gauge (mm) Gross weight (kg) Length (mm) Width (mm) Height (mm) Gross weight (kg)
100 6
6.3
10
±5
±2×2.5
0.4 Yyn0 or Dyn11 405 2165 1765 4 2.0 40 1000 520 1030 400 720 1300 1000 1400 980 M10 (a)40×4
125 480 2590 2115 1.8 42 1000 520 1050 400 800 1300 1000 1400 1060 M10 (a)40×4
160 560 3100 2530 1.8 42 1050 670 1080 550 880 1500 1100 1400 1100 M10 (a)40×4
200 655 3970 3240 1.6 42 1070 670 1150 550 900 1500 1100 1600 1120 M10 (a)40×1
250 760 4675 3815 1.6 43 1100 670 1200 550 1070 1500 1100 1600 1300 M10 (a)40×6
315 880 5610 4575 1.1 45 1130 780 1220 500×660 1200 1500 1250 1600 1450 M10 (a)40×6
400 1040 6630 5410 1.4 45 1170 780 1290 660 1350 1500 1250 1600 1600 M10 (b)60×6
500 1200 7945 6480 1.4 45 1220 780 1355 660 1570 1700 1250 1800 1800 M10 (b)60×6
630 1400 9265 7560 1.3 45 1300 780 1380 660 1700 1700 1250 1800 1950 M10 (c)80×8
630 1345 9775 7975 1.3 45 1380 780 1250 660 1680 1700 1250 1800 1930 M10 (c)80×8
800 1695 11560 9430 1.3 46 1450 940 1295 680×820 2050 1900 1500 1800 2340 M10 (c)80×8
1000 1985 13345 10885 1.1 46 1470 940 1380 680×820 2310 1900 1500 1800 2600 M10 (d)100×10
1250 2385 15640 12760 6 1.1 47 1570 940 1515 820 2790 1900 1500 2000 3100 M10 (d)100×10
1600 2735 18105 14770 1.1 48 1660 940 1650 820×1070 3500 1900 1500 2000 3830 M10 (e)120×10
2000 3320 21250 17335 1.0 48 1710 1090 1750 820×1070 4200 2100 1650 2000 4600 M10 (d)120×12
2500 4000 24735 20180 1.0 49 1750 1190 1815 820×1070 4725 2100 1650 2000 5200 M10 (d)120×12